亚洲春色中文字幕_免费99精品国产自在现??_—级v免费大片国产_日韩人妻无码aⅴ一区二区_婷婷丁香五月激情综合_久草综合精品zc_久久美女一级黄色电影_╳╳╳无尽性视频漫画_免费天堂无码成人AV电影在线观看_青青揄拍视频

Leave Your Message
*姓名不能為空!
* 留言內(nèi)容不能為空!
Product
Recommended products

Single speed fan controller

This series of single-speed fan controller is a high-performance product specially launched in response to market demand for low-power fans below 22KW. It is mainly used for smoke exhaust, fire control, etc.

    Product overview

    ?

    This series of single-speed fan controller is a high-performance product specially launched in response to market demand for low-power fans below 22KW. It is mainly used for smoke exhaust, fire control, etc.

    ?

    Model description

    Model description.jpg

    W1:153mm H1:91mm W2:144mm

    H2:81mm D: 30mm

    ?

    Wiring port description

    ?

    Terminal number

    illustrate

    Terminal number

    illustrate

    1

    Working power supply AC220V live wire

    9

    Remote control point/on start, off stop

    ?

    Control in automatic state

    2

    Working power supply AC220V neutral line

    10/11

    DC24V fire start/start with power, stop with power loss

    3

    Contactor coil control point

    12/13

    DC24V forced start/start with power, stop with power loss

    any status

    4

    Manual feedback

    14

    Start/jog signal

    Manual/automatic state programmable

    ?

    5

    Public terminal (passive)

    15

    Stop/jog signal

    6

    automatic feedback

    16

    Forced start and stop

    any status

    7

    Public signal control terminal

    17

    ?

    Fault protection signal point/normally open and normally closed programmable

    ?

    ?

    ?

    8

    Fire damper contact/normally closed

    ?

    Automatic signal wiring

    ?

    Fire damper: connected to 7#, 8# (connected to normally closed);

    Remote control: connect 7#, 9# (start when connected, stop when disconnected)

    Fire center control: connect to 10#, 11# (DC24V has no positive or negative distinction)

    Forced start control: connect 12#, 13# (DC24V has no positive or negative distinction);

    Passive forced start: connect 7#, 14# (start when connected, stop when disconnected).

    ?

    Function operation description

    ?

    Power-off memory saving function

    This product has a power-off memory saving function. When the power is turned on again after a power outage, it will default to the state before the power outage. For example: when it is in manual mode, the power is off, and when it is powered on, it is in manual mode.

    Fault type selection

    In the automatic state, press and hold the "Start" button for more than 5 seconds to switch the fault signal type of terminal 15#, which is divided into normally open type and normally closed type. The factory default is normally open type.

    Protection type selection

    In the automatic state, press and hold the "Stop" button for more than 5 seconds to change the fault protection type of terminal 15 to the fault alarm type. It only alarms but does not disconnect the output, and switches the fault protection type in sequence.

    ?

    Wiring schematic diagram

    ?

    Single speed fan controller.jpg

    ?

    Dimensional drawing

    ?

    Single water pump controller 1.jpg